The Thermostat Is Set for a 1960s Man: Testing Thermal Alliesthesia and Personal Comfort Systems Against Heating the Whole Room

Somewhere in your home or office there is a number on a dial, and an argument about it. One person wants it warmer, another cooler, and the compromise leaves nobody happy. The usual assumption is that the room is the thing to be heated or cooled. A growing body of research points to a different target: the person. Warming a pair of hands, a lap or a pair of feet takes a few watts. Warming a whole building to the same effect takes hundreds, and most of that heat goes to air and walls that nobody feels.

There is also a popular story behind this idea, and it needs a careful look. The story says that the formulas behind building comfort standards were built around an average man of the 1960s, so offices are tuned to the wrong body. After reading the original study, the standards experts’ reply, a critical news analysis, a pilot study on why warmth feels pleasant, a field trial of heated and cooled office chairs, two sets of building-energy simulations, a small chamber experiment on personal heaters and the World Health Organization’s guidance on cold homes, my verdict is a real shared mechanism, with the headline claim about a biased standard overstated. The part that holds up is that local warmth can stand in for degrees of room heat. The part that does not exist yet is evidence from ordinary homes. The proposal is a way to test it.

Scientific Foundation

Begin with the claim that made headlines. In 2015, Boris Kingma and Wouter van Marken Lichtenbelt published a paper in Nature Climate Change arguing that the metabolic rate values in the thermal comfort model behind building standards come from an average man, and may overestimate female metabolic rate by up to 35 percent. They noted that homes and offices account for about 30 percent of carbon dioxide emissions and that occupant behavior accounts for about 80 percent of the variation in energy use. Their argument was that if buildings are set for the wrong metabolism, they may waste energy keeping some occupants comfortable. The page I could read gave only the abstract, so I could not see the design, the sample or the stated limitations, and the up-to-35-percent figure is attributed in the abstract to a cited source and not to their own measurement [1].

The reply from the standards side is worth reading in full. Bjarne Olesen, a former chair of the committee behind the American standard, wrote that the experiment behind the paper involved 16 sedentary women and had no male comparison group doing the same work, which he called inconclusive. He says the standards table lists offices at about 1.2 met, a unit of activity, and that metabolic rate serves as a stand-in for activity in an empirical formula, not as a heat-balance input. Studies that included equal numbers of men and women found they preferred nearly the same temperatures: in work he cites, men preferred 25.4 degrees Celsius and women 25.8 in one pair of samples, and 25.0 against 25.1 in another with 32 people per sex. Women’s lower metabolism is offset by slightly lower skin temperature and evaporative loss. Women often feel colder in summer offices, he says, partly because of lighter clothing, and a meta-analysis he cites found women more likely to report dissatisfaction in cool conditions, with a ratio of 1.74. He also cites a survey of 100 offices finding summer indoor temperatures around 22.9 degrees, below the recommended range [2].

A news analysis in Workplace Insight, from a writer who calls the original story flimsy, adds that the American standard’s comfort index rests on research with over 1,000 subjects in equal numbers of men and women. It notes that the study’s reference man was a 40-year-old weighing about 154 pounds, based on 1960s measurements, and that the study ignored clothing, non-sedentary work and personal preference [3]. So the strong form of the story, that standards are built for men and fail women, is disputed by the people who wrote them, and what remains is a narrower point: comfort differs between people, and a single setting cannot fit everyone.

That narrower point has a physiological basis, and the concept is called alliesthesia, a word coined by the physiologist Michel Cabanac. It holds that the same temperature change can feel pleasant or unpleasant depending on whether it helps restore the body to its normal thermal state. A pilot study by Parkinson and colleagues tested six healthy young men who moved between rooms at 16, 23 and 30 degrees, with periods of cycling in between. The same step change felt pleasant after cycling, when the body was warm, and unpleasant when the men were sedentary. Pleasure tracked the rate of change in skin temperature, and it was short-lived. The authors describe it as preliminary, with only six participants, all male, in field-laboratory conditions, and they note the central criticism of the theory, that displeasure must come before pleasure [4].

Now the engineering. A field trial described in the ASHRAE Journal tested personal comfort systems in the form of battery-powered mesh office chairs with fans and heating strips. Forty workers at a government office in Redwood City, California, used them for three months. Acceptability was 96 percent across operative temperatures from 20.5 to 24.5 degrees, which is 69 to 76 degrees Fahrenheit, and users were 99 percent satisfied by the end of the study. The chairs drew a maximum of 16 watts, compared with roughly 500 to 700 watts per occupant for a conventional air-conditioning system during occupied hours, and users ran the heating or cooling about 77 percent of the time they sat. Total energy savings were unknown, since some products were not yet commercial, and the study covered one building over three months [5].

Simulations suggest what the savings might be at the building level. A study from Berkeley’s building research group simulated six medium-sized office buildings across seven climate zones. Raising the cooling setpoint from 22.2 to 25 degrees saved an average of 29 percent of cooling energy and 27 percent of total air-conditioning energy, which the abstract says was without reducing satisfaction. Lowering the heating setpoint from 21.1 to 20 degrees saved an average of 34 percent of terminal heating energy. Wider temperature bands made possible by fans or personal controls produced savings of 32 to 73 percent depending on climate. These are simulations, validated against monitored buildings in a way the abstract does not detail, and the satisfaction assumption is stated and not shown [6].

For heating, a Strathclyde team simulated an electric heated desk of 170 watts using a model of the human body in 25 segments. Thermal sensation shifted about half a scale point colder for each degree the room air was lowered. With the desk off, feet, legs and hands suffered most, and with the desk on, those parts moved toward neutral. The authors judged 18 degrees acceptable with the desk and used it as the lower setpoint in their energy runs. Moving from 21 to 18 degrees cut annual heating demand by about 27 percent in Aberdeen and London and 16 percent in Montreal for a four-storey office. The paper’s headline ranges do not match each other, so the exact savings should be treated with caution. The comfort runs assumed fixed clothing and activity, and no real people took part [7].

A chamber experiment at Eindhoven University of Technology, reported in a news summary of a doctoral thesis by Michal Veselý, tested personalized heaters with 13 subjects at an operative temperature of 18 degrees. A heated chair, a heated desk mat and the full system with a floor mat each significantly improved comfort, the chair was the most effective single heater, and automatic control based on hand skin temperature matched user control. The simulation part found that lowering the setpoint while using personal heating to offset cold discomfort considerably reduced thermal energy demand, though the summary gives no percentage. The test had 13 people and one condition [8].

Finally, a warning from public health. The World Health Organization’s housing guidelines recommend 18 degrees as a safe and well-balanced indoor temperature for general populations in cold seasons, a strong recommendation, and state that a higher minimum may be necessary for older people, children and people with chronic illness, especially heart and lung disease. In the evidence the guidelines review, all six studies on blood pressure found lower indoor temperatures associated with higher blood pressure, with moderate certainty. The guidelines also acknowledge that evidence cannot say exactly where harm begins [9].

Cross-Domain Connection

Put these threads together and the shape of an idea appears. Building engineers have measured the effect of widening a temperature band and found large simulated savings. Physiologists have found that the body prizes the correction of a local imbalance, such as cold hands, more than it values a uniform environment. Small devices exist that heat the body directly for a few watts. Heating the room to warm the person is like lighting a bonfire to toast one marshmallow: the marshmallow gets warm, and so does the whole field.

The following is my own proposal and not an existing program. I will call it heating the body ahead of the room. Choose a whole-room temperature that is a little lower than the one you use now, but never below the safe floor of 18 degrees, and higher for older people, children and anyone with heart or lung disease [9]. Offset the drop with low-wattage warmth applied where the body feels cold soonest: a heated seat pad, a heated throw over the lap, a foot warmer. Those are the body parts the Strathclyde model found most affected by cold [7], and the chair experiments found them effective in comfort tests [5][8]. Use timers or sensors so devices are off when nobody is sitting.

The arithmetic from the sources shows the scale, with my own multiplication. The office chair drew at most 16 watts against 500 to 700 watts per occupant for air conditioning, a ratio of roughly 31 to 44 times [5]. Eight hours at 16 watts is 0.128 kilowatt-hours. A 170-watt desk for eight hours is 1.36 kilowatt-hours [7]. These are modest numbers beside heating a whole room for the same period, though a room’s heat load depends on insulation, climate and fuel, none of which I can estimate from these sources. As far as I know, heating with electricity at the point of use will save less where the main heating comes from an efficient heat pump, and that is my reasoning, not a finding from the papers I read.

Alliesthesia suggests one more twist, which is a hypothesis of mine. If the body rewards correcting a cold spot with a pleasant sensation, a small heater that warms cold hands could feel disproportionately good compared with its energy cost [4]. Pleasure at the point of correction might make people more tolerant of a cooler room, which is what the simulated savings depend on. The pilot study did not test that, and it showed the pleasure fades quickly [4], so the effect may be brief.

What Remains Undemonstrated

The biggest gap is the home. The real-world trial I found was in an office, with 40 workers over three months, one building, and a design that varied the chair and not the household [5]. The simulations are of offices [6][7], and the chamber study had 13 people at one temperature [8]. I found no measured study of what happens to total energy use and comfort when a household lowers its thermostat and adds personal heaters. Without measurement, the savings might be partly or wholly offset if people leave devices on all the time, as users ran the chairs about 77 percent of the time they sat [5], or if the electricity comes from a more carbon-intensive or more expensive source than the fuel it replaces.

The strong claim about biased standards is not established. The original study’s reported design, as described by critics, had 16 women and no male comparison group [2][3], and I could not read the full paper to check [1]. The standards side reports little difference between men and women in controlled studies [2]. My own reading is that the evidence supports different people preferring different temperatures, which is a reason for personal control, and does not support the claim that the dial is wrong for all women.

Alliesthesia has thin experimental support in building research. The pilot used six young men, and the authors call the theory largely theoretical and note that its central criticism is unresolved [4]. The simulations rely on fixed assumptions for clothing and activity, which may not describe a home [7]. The two sets of simulated savings do not agree with each other in size, and one paper’s own figures are inconsistent [6][7].

Health is the most serious open question. Lowering indoor temperatures might harm vulnerable people, and the guidelines say a higher minimum may be needed for some [9]. A personal heater may protect hands and feet without protecting the core or the blood pressure that responds to ambient cold, and no study I read tested that [9]. I also did not read anything on the safety of heated devices in homes, which is a real concern for sleepers and for people with reduced sensation.

The trial I propose is a randomized household study across one winter. Recruit households in a single climate with metered heating and electricity. Give one group usual practice. Give another a modest, safe thermostat reduction with a floor of 18 degrees, higher for vulnerable members. Give a further group the same reduction plus a set of low-wattage personal heaters with timers. Measure total household energy and cost from meters, comfort votes taken a few times a week, and for older participants home blood pressure readings. Record device hours and any safety incidents. What would prove the idea wrong is no net energy saving after counting the devices, worse comfort than the other groups, any rise in blood pressure or cold-related symptoms in vulnerable participants, or devices running most of the day.

Why It Matters

Heating and cooling are a large share of household energy, and the whole-room method treats everyone the same. Heating the body ahead of the room might cut waste without asking anyone to be uncomfortable, which matters because lectures about wearing a sweater rarely change behavior. The office evidence suggests that giving people a small amount of control over their own warmth was associated with acceptability across a wider range of room temperatures in one building [5]. If that carries over to homes, the benefit would be both a lower bill and fewer thermostat quarrels.

There is an equity angle that cuts both ways. People struggling to pay for heat could gain from a cheap way to stay comfortable at a lower setting. But the WHO guidance is a reminder that cold itself is harmful, and a scheme that nudges poorer or older households to keep rooms colder could do damage [9]. Any version of the idea has to protect the safe floor as the priority and treat saving energy as the lesser goal.

Human Dimension

Every household has someone who sits under a blanket in January while someone else opens a window. The blanket is the oldest personal comfort system there is, and nobody thinks of it as a technology. What the research adds is a way to take that instinct seriously: to let each person fix their own cold spot, and to let the room be a little cooler for everyone. It turns an argument into an arrangement. The person who is always cold gets a warm lap, the person who is always hot gets a cooler room, and the bill goes down a little. There is some dignity in the arrangement too, since it treats each person’s body as the thing worth caring for and not as a problem for the thermostat to average away.

Sources

  1. Kingma and van Marken Lichtenbelt, “Energy consumption in buildings and female thermal demand,” Nature Climate Change, 2015 (abstract page only; the design, sample and limitations were not visible; the up-to-35-percent figure is attributed in the abstract to a cited source; I read a summary produced by the fetch tool), https://www.nature.com/articles/nclimate2741.pdf
  2. Bjarne Olesen, “Are women feeling colder than men in air conditioning buildings?” REHVA Journal (a response by a former chair of the American comfort standard committee; critique of the 16-woman study; figures from earlier studies cited by the author; I read a summary produced by the fetch tool), https://www.rehva.eu/rehva-journal/chapter/are-women-feeling-colder-than-men-in-air-conditioning-buildings
  3. Workplace Insight, “That story about sexist air conditioning systems roundly debunked” (news analysis by a critic of the original coverage; quotes from the standards committee; I read a summary produced by the fetch tool), https://workplaceinsight.net/that-story-about-sexist-air-conditioning-systems-roundly-debunked
  4. Parkinson and colleagues, “Perception of Transient Thermal Environments: Pleasure and Alliesthesia” (pilot study with six healthy young men; the authors describe it as preliminary; I read a summary produced by the fetch tool), https://www.researchgate.net/profile/Thomas_Parkinson2/publication/268688166_Perception_of_Transient_Thermal_Environments_Pleasure_and_Alliesthesia/links/5517d52a0cf2d70ee2792e75.pdf
  5. ASHRAE Journal, “Personal comfort systems study collects data to better predict occupant thermal comfort” (field study of heated and cooled office chairs with 40 workers over three months in one building; total savings unknown; I read a summary produced by the fetch tool), https://www.ashrae.org/news/ashraejournal/personal-comfort-systems-study-collects-data-to-better-predict-occupant-thermal-comfort
  6. Hoyt and colleagues, “Extending air temperature setpoints: Simulated energy savings and design considerations for new and retrofit buildings,” Building and Environment (abstract record at eScholarship; simulation of six office buildings in seven climate zones; no limitations stated in the abstract; I read a summary produced by the fetch tool), https://escholarship.org/uc/item/13s1q2xc
  7. Rida and Kelly, 2024, “Reducing energy consumption in urban office buildings with localised heating and heating set point temperature reductions” (University of Strathclyde repository; simulation study with a 170-watt heated desk; the paper’s headline savings ranges are inconsistent with its case results; no human participants; I read a summary produced by the fetch tool), https://strathprints.strath.ac.uk/91651/1/Rida-and-Kelly-2024-Reducing-energy-consumption-in-urban-office-buildings-with-localised-heating-and-heating-set-point-temperature-reductions.pdf
  8. Eindhoven University of Technology, news summary of Michal Veselý’s doctoral research on personalized heating control systems (13 subjects in a climate chamber at 18 degrees; no percentage savings given; a news summary and not the thesis; I read a summary produced by the fetch tool), https://www.tue.nl/en/news-and-events/news-overview/personalized-heating-control-systems-to-improve-thermal-comfort-and-reduce-energy-consumption
  9. World Health Organization, Housing and Health Guidelines, 2018, chapter on indoor cold (18 degrees recommended as a safe temperature for general populations, strong recommendation; higher minimum may be needed for vulnerable groups; moderate-certainty evidence on blood pressure; the insulation certainty rating is inconsistent within the chapter; I read a summary produced by the fetch tool), https://www.ncbi.nlm.nih.gov/books/NBK535294/